Skip to content
  • There are no suggestions because the search field is empty.

Diagnosing Velit AC Not Blowing Cold

How to determine if an AC unit is repairable with parts or if it needs replacement

Below is a flowchart used to determine why a Velit AC unit may not be producing cooled air.  Below the flowchart each step is broken down with instructions. Disclaimer: This flowchart should only be used as basic diagnostic guidance only.

whiteboard_exported_image-1

Video: AC Not Blowing Cold


Additional Instructions for Each Step:

Step 1: Set the system

Set the unit to Turbo Mode and adjust the temperature to the lowest setting.


Step 2: Check the ambient temperature.

  • Is it at least 67°F (20°C)?

If NO:

  • Try again on a warmer day. The unit may enter anti-frost protection at low temperatures.

If YES:

  • Continue to the next step.

Step 3: Power

Check the power consumption.

  • Does the unit draw more than 100 watts?

If YES:

  • The compressor is running.
  • Likely causes: refrigerant leak or internal blockage.
  • Action: Replace the unit.

If NO:

  • The compressor is not running.
  • Likely causes: electrical components or wiring issue — generally easier to fix and should take 5–30 minutes.
  • Action: Proceed to the next step.

Step 4: Outside fan

Is the outside fan running?

  • The outside fan is controlled by the DC controller.

If YES:

  • The controller receives signals from the display panel.
  • Likely issue: DC control problem.
  • Action: Replace the controller.

If NO:

  • Check the display panel that sends the control signal.
  • Action: Continue troubleshooting.

Step 5: Display Panel Connectors

  1. Pop the display panel off and reseat the 4-pin connector.
  2. Check if the system draws more than 150W.
  3. Measure voltage between the black and green wires using a multimeter:
    1. Should read above 5V.

If the voltage is below 5V or the customer cannot get a reading:

  • Action: Replace the display panel.
  • Note: If the customer canThe issue may not actually be the display panel, but this is the first step to isolate the problem.

Step 6: Measure

Measure voltage at the display connector.

  • Does pin 3 to pin 2 read 5V?

If NO:

  • Action: Replace the display panel.

If YES:

  • Continue to the next step.


 

See the image below, you want to measure voltage between pins 2 and 3 as shown at bottom of chart. 

Step 7: Reseat and tighten

  • Reseat the 12-pin connector on the controller. Check that all wire connections on the DC Controller and Compressor are tight. Retest Unit. If this still does not work, replace the DC Controller.